Home › Calculators › Voltage drop

Voltage drop calculator

Voltage drop and power lost in the wire for a DC string or an AC circuit, plus the smallest size that meets your target. Uses NEC Chapter 9 Table 8 resistances.

How it works

Voltage drop = 2 × one-way length × current × resistance per foot for DC and single-phase AC, and √3 × length × current × resistance for three-phase. Resistance is the DC value at 75 °C from NEC Chapter 9 Table 8 for stranded uncoated copper or aluminum.

For AC this leaves out inductive reactance, which is small for the wire sizes used in residential solar. For large three-phase feeders, use the AC impedance from Chapter 9 Table 9.

Power lost in the wire is the voltage drop × current. On a solar circuit that energy is lost every sunny hour for the life of the system, so it is often worth one size larger than ampacity alone requires.

Questions

What is a good voltage drop for a solar string?

Most designers keep DC strings under 1–2% at the operating current. Long ground-mount runs often justify a larger conductor.

Does voltage drop affect safety?

Not directly. Ampacity decides safety; voltage drop decides how much energy you lose and whether the inverter sees enough voltage.

Estimates only, based on NEC 2020/2023 tables. Check the code edition your jurisdiction uses, the equipment datasheets and your AHJ before you build.