Home › Compatibility › JA Solar JAM54S31-405/MR + Fronius Primo GEN24 7.7 Plus

JA Solar JAM54S31-405/MR with Fronius Primo GEN24 7.7 Plus

Compatibility and string sizing for this panel and hybrid inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 3–14 panels work. The longest string reaches 568 V on the coldest morning, under the 600 V inverter limit. One Fronius Primo GEN24 7.7 Plus takes up to 2 strings of 13: 26 panels, 10.53 kWp DC, DC/AC ratio 1.37.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C3–14 panels per string (best 12)
Chicago, IL−21 °C3–14 panels per string (best 13)
Denver, CO−23.6 °C3–14 panels per string (best 13)
Atlanta, GA−9.5 °C3–14 panels per string (best 13)
Dallas, TX−7.1 °C3–14 panels per string (best 13)
Phoenix, AZ1.3 °C3–15 panels per string (best 14)
Miami, FL5.9 °C3–15 panels per string (best 14)

Common system sizes

How JA Solar JAM54S31-405/MR panels lay out on the Fronius Primo GEN24 7.7 Plus for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW151 × 8 + 1 × 7 panels on 1 inverter6.08 kWp0.79
About 8 kW202 strings of 10 on 1 inverter8.10 kWp1.05
About 10 kW251 × 13 + 1 × 12 panels on 1 inverter10.12 kWp1.32