Home › Compatibility › JA Solar JAM54S31-405/MR + Hoymiles HMS-800-2T-NA

JA Solar JAM54S31-405/MR with Hoymiles HMS-800-2T-NA

Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.

✓

Compatible

Yes. Each HMS-800-2T-NA takes 2 panels, and up to 5 units fit on one 20 A branch circuit (10 panels). DC/AC ratio 1.12.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C2 panels per unit
Chicago, IL−21 °C2 panels per unit
Denver, CO−23.6 °C2 panels per unit
Atlanta, GA−9.5 °C2 panels per unit
Dallas, TX−7.1 °C2 panels per unit
Phoenix, AZ1.3 °C2 panels per unit
Miami, FL5.9 °C2 panels per unit

Common system sizes

How JA Solar JAM54S31-405/MR panels lay out on the Hoymiles HMS-800-2T-NA for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW158 × HMS-800-2T-NA on 2 branch circuits6.08 kWp1.05
About 8 kW2010 × HMS-800-2T-NA on 2 branch circuits8.10 kWp1.12
About 10 kW2513 × HMS-800-2T-NA on 3 branch circuits10.12 kWp1.08