Home › Compatibility › Jinko Solar Tiger Neo JKM425N-54HL4-B + APsystems QS1
Jinko Solar Tiger Neo JKM425N-54HL4-B with APsystems QS1
Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.
✓
Compatible
Yes. Each QS1 takes 4 panels, and up to 3 units fit on one 20 A branch circuit (12 panels). DC/AC ratio 1.42.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- ✓ Max input voltageVoc at the record low is 42.4 V, within the 60 V limit (71%).
- ✓ MPPT window, hot dayVmp on the hottest day is 27.4 V, inside 22–48 V.
- ✓ MPPT window, cold dayVmp on the coldest day is 36.2 V, inside the MPPT range.
- ✓ Start-up voltageHot-day Voc 34.4 V clears the 20 V start-up voltage.
- ✓ Input currentImp 13.13 A is within the 14 A max input current. The datasheet gives no separate Isc limit.
- ✓ Module power pairing425 W is inside the recommended 250–525 (DC/AC 1.42).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 4 panels per unit |
| Chicago, IL | −21 °C | 4 panels per unit |
| Denver, CO | −23.6 °C | 4 panels per unit |
| Atlanta, GA | −9.5 °C | 4 panels per unit |
| Dallas, TX | −7.1 °C | 4 panels per unit |
| Phoenix, AZ | 1.3 °C | 4 panels per unit |
| Miami, FL | 5.9 °C | 4 panels per unit |
Common system sizes
How Jinko Solar Tiger Neo JKM425N-54HL4-B panels lay out on the APsystems QS1 for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 14 | 4 × QS1 on 2 branch circuits | 5.95 kWp | 1.24 |
| About 8 kW | 19 | 5 × QS1 on 2 branch circuits | 8.07 kWp | 1.35 |
| About 10 kW | 24 | 6 × QS1 on 2 branch circuits | 10.20 kWp | 1.42 |