Jinko Solar Tiger Neo JKM590N-72HL4-BDV with Solis S6-GC50K-US
Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.
Compatible
Yes. At a −10 °C record low and a 40 °C hot day, strings of 5–17 panels work. The longest string reaches 959 V on the coldest morning, under the 1000 V inverter limit. One Solis S6-GC50K-US takes up to 8 strings of 17: 136 panels, 80.24 kWp DC, DC/AC ratio 1.60.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.
- Voc on the coldest morning51.86 V × (1 + -0.25%/°C × (−10 − 25)) = 56.40 V per panel.
- Vmp on the hottest afternoonCells reach 71.2 °C (40 °C air plus the NMOT rise), so Vmp drops from 42.88 V to 36.24 V (Vmp coefficient taken as Pmax − Isc coefficient).
- Longest string1000 V inverter limit ÷ 56.40 V = 17 panels.
- Shortest string180 V MPPT minimum ÷ 36.24 V = 5 panels; start-up voltage needs 4.
- Strings per MPPTHot-day Isc 16.27 A per string, so the MPPT inputs take 2 + 2 + 2 + 2 string(s).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 5–17 panels per string (best 17) |
| Chicago, IL | −21 °C | 5–17 panels per string (best 17) |
| Denver, CO | −23.6 °C | 5–17 panels per string (best 17) |
| Atlanta, GA | −9.5 °C | 5–17 panels per string (best 17) |
| Dallas, TX | −7.1 °C | 5–17 panels per string (best 17) |
| Phoenix, AZ | 1.3 °C | 5–18 panels per string (best 18) |
| Miami, FL | 5.9 °C | 5–18 panels per string (best 18) |
Common system sizes
How Jinko Solar Tiger Neo JKM590N-72HL4-BDV panels lay out on the Solis S6-GC50K-US for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| 1 inverter, fully loaded | 136 | 8 strings of 17 on 1 inverter | 80.24 kWp | 1.60 |
| 2 inverters, fully loaded | 272 | 16 strings of 17 on 2 inverters | 160.48 kWp | 1.60 |
| 4 inverters, fully loaded | 544 | 32 strings of 17 on 4 inverters | 320.96 kWp | 1.60 |