Home › Compatibility › LONGi Hi-MO 6 LR5-54HTB-435M + Sol-Ark 30K-3P-208V

LONGi Hi-MO 6 LR5-54HTB-435M with Sol-Ark 30K-3P-208V

Compatibility and string sizing for this panel and hybrid inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 6–12 panels work. The longest string reaches 514 V on the coldest morning, under the 550 V inverter limit. One Sol-Ark 30K-3P-208V takes up to 7 strings of 12: 84 panels, 36.54 kWp DC, DC/AC ratio 1.22.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C6–12 panels per string (best 12)
Chicago, IL−21 °C6–12 panels per string (best 12)
Denver, CO−23.6 °C6–12 panels per string (best 12)
Atlanta, GA−9.5 °C6–12 panels per string (best 12)
Dallas, TX−7.1 °C6–12 panels per string (best 12)
Phoenix, AZ1.3 °C6–13 panels per string (best 13)
Miami, FL5.9 °C6–13 panels per string (best 13)

Common system sizes

How LONGi Hi-MO 6 LR5-54HTB-435M panels lay out on the Sol-Ark 30K-3P-208V for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded888 strings of 11 on 1 inverter38.28 kWp1.28
2 inverters, fully loaded17616 strings of 11 on 2 inverters76.56 kWp1.28
4 inverters, fully loaded35232 strings of 11 on 4 inverters153.12 kWp1.28