Qcells Q.TRON BLK M-G2+ 430 with Fronius Symo 17.5-3 480

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 8–23 panels work. The longest string reaches 980 V on the coldest morning, under the 1000 V inverter limit. One Fronius Symo 17.5-3 480 takes up to 2 strings of 21: 42 panels, 18.06 kWp DC, DC/AC ratio 1.03.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C8–22 panels per string (best 20)
Chicago, IL−21 °C8–22 panels per string (best 21)
Denver, CO−23.6 °C8–22 panels per string (best 20)
Atlanta, GA−9.5 °C8–23 panels per string (best 21)
Dallas, TX−7.1 °C8–23 panels per string (best 21)
Phoenix, AZ1.3 °C8–24 panels per string (best 22)
Miami, FL5.9 °C8–24 panels per string (best 22)

Common system sizes

How Qcells Q.TRON BLK M-G2+ 430 panels lay out on the Fronius Symo 17.5-3 480 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded524 strings of 13 on 1 inverter22.36 kWp1.28
2 inverters, fully loaded1048 strings of 13 on 2 inverters44.72 kWp1.28
4 inverters, fully loaded20816 strings of 13 on 4 inverters89.44 kWp1.28