REC REC405AA Pure with SMA SB6.0-1SP-US-41

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 3–11 panels work. The longest string reaches 582 V on the coldest morning, under the 600 V inverter limit. One SMA SB6.0-1SP-US-41 takes up to 2 strings of 11: 22 panels, 8.91 kWp DC, DC/AC ratio 1.49.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C3–10 panels per string (best 10)
Chicago, IL−21 °C3–11 panels per string (best 11)
Denver, CO−23.6 °C3–11 panels per string (best 11)
Atlanta, GA−9.5 °C3–11 panels per string (best 11)
Dallas, TX−7.1 °C3–11 panels per string (best 11)
Phoenix, AZ1.3 °C3–11 panels per string (best 11)
Miami, FL5.9 °C3–11 panels per string (best 11)

Common system sizes

How REC REC405AA Pure panels lay out on the SMA SB6.0-1SP-US-41 for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW151 × 8 + 1 × 7 panels on 1 inverter6.08 kWp1.01
About 8 kW202 strings of 10 on 1 inverter8.10 kWp1.35
About 10 kW251 × 9 + 2 × 8 panels on 2 inverters10.12 kWp0.84