Home › Compatibility › REC REC450AA Pure-RX + SMA SB5.0-1SP-US-41

REC REC450AA Pure-RX with SMA SB5.0-1SP-US-41

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 3–8 panels work. The longest string reaches 563 V on the coldest morning, under the 600 V inverter limit. One SMA SB5.0-1SP-US-41 takes up to 2 strings of 8: 16 panels, 7.20 kWp DC, DC/AC ratio 1.44.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C3–8 panels per string (best 8)
Chicago, IL−21 °C3–8 panels per string (best 8)
Denver, CO−23.6 °C3–8 panels per string (best 8)
Atlanta, GA−9.5 °C3–8 panels per string (best 8)
Dallas, TX−7.1 °C3–8 panels per string (best 8)
Phoenix, AZ1.3 °C3–8 panels per string (best 8)
Miami, FL5.9 °C3–8 panels per string (best 8)

Common system sizes

How REC REC450AA Pure-RX panels lay out on the SMA SB5.0-1SP-US-41 for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW131 × 7 + 1 × 6 panels on 1 inverter5.85 kWp1.17
About 8 kW183 strings of 6 on 2 inverters8.10 kWp0.81
About 10 kW221 × 8 + 2 × 7 panels on 2 inverters9.90 kWp0.99