Talesun BiPro TM7G54M-425 with Fronius Symo 15.0-3 480
Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.
Compatible
Yes. At a −10 °C record low and a 40 °C hot day, strings of 8–24 panels work. The longest string reaches 1,000 V on the coldest morning, under the 1000 V inverter limit. One Fronius Symo 15.0-3 480 takes up to 2 strings of 22: 44 panels, 18.70 kWp DC, DC/AC ratio 1.25.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.
- Voc on the coldest morning38.3 V × (1 + -0.25%/°C × (−10 − 25)) = 41.65 V per panel.
- Vmp on the hottest afternoonCells reach 71.2 °C (40 °C air plus the NMOT rise), so Vmp drops from 31.7 V to 26.63 V (Vmp coefficient taken as Pmax − Isc coefficient).
- Longest string1000 V inverter limit ÷ 41.65 V = 24 panels.
- Shortest string200 V MPPT minimum ÷ 26.63 V = 8 panels.
- Strings per MPPTHot-day Isc 15.90 A per string, so the MPPT inputs take 3 + 2 string(s); expect about 34.1% current clipping at peak.
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 8–23 panels per string (best 21) |
| Chicago, IL | −21 °C | 8–23 panels per string (best 21) |
| Denver, CO | −23.6 °C | 8–23 panels per string (best 21) |
| Atlanta, GA | −9.5 °C | 8–24 panels per string (best 22) |
| Dallas, TX | −7.1 °C | 8–24 panels per string (best 22) |
| Phoenix, AZ | 1.3 °C | 8–24 panels per string (best 23) |
| Miami, FL | 5.9 °C | 8–24 panels per string (best 23) |
Common system sizes
How Talesun BiPro TM7G54M-425 panels lay out on the Fronius Symo 15.0-3 480 for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| About 6 kW | 14 | 1 string of 14 on 1 inverter | 5.95 kWp | 0.40 |
| About 8 kW | 19 | 1 string of 19 on 1 inverter | 8.07 kWp | 0.54 |
| About 10 kW | 24 | 1 string of 24 on 1 inverter | 10.20 kWp | 0.68 |