Talesun BiPro TM7G72M-585 with Hoymiles HMS-1600-4T-NA

Compatibility and string sizing for this panel and microinverter, calculated from both datasheets.

!

Compatible, with a caution

Yes. Each HMS-1600-4T-NA takes 4 panels, and up to 2 units fit on one 20 A branch circuit (8 panels). DC/AC ratio 1.62. Check the Input current; Module power pairing below.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C4 panels per unit (check: Input current)
Chicago, IL−21 °C4 panels per unit (check: Input current)
Denver, CO−23.6 °C4 panels per unit (check: Input current)
Atlanta, GA−9.5 °C4 panels per unit (check: Input current)
Dallas, TX−7.1 °C4 panels per unit (check: Input current)
Phoenix, AZ1.3 °C4 panels per unit (check: Input current)
Miami, FL5.9 °C4 panels per unit (check: Input current)

Common system sizes

How Talesun BiPro TM7G72M-585 panels lay out on the Hoymiles HMS-1600-4T-NA for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW103 × HMS-1600-4T-NA on 2 branch circuits5.85 kWp1.35
About 8 kW144 × HMS-1600-4T-NA on 2 branch circuits8.19 kWp1.42
About 10 kW175 × HMS-1600-4T-NA on 3 branch circuits9.95 kWp1.38