Talesun BiPro TM7G72M-585 with Sol-Ark 60K-3P-480V

Compatibility and string sizing for this panel and hybrid inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 4–17 panels work. The longest string reaches 961 V on the coldest morning, under the 1000 V inverter limit. One Sol-Ark 60K-3P-480V takes up to 7 strings of 17: 119 panels, 69.61 kWp DC, DC/AC ratio 1.16.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C, bifacial gain 10%.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C4–17 panels per string (best 16)
Chicago, IL−21 °C4–17 panels per string (best 16)
Denver, CO−23.6 °C4–17 panels per string (best 16)
Atlanta, GA−9.5 °C4–17 panels per string (best 17)
Dallas, TX−7.1 °C4–17 panels per string (best 17)
Phoenix, AZ1.3 °C4–18 panels per string (best 17)
Miami, FL5.9 °C4–18 panels per string (best 18)

Common system sizes

How Talesun BiPro TM7G72M-585 panels lay out on the Sol-Ark 60K-3P-480V for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded1288 strings of 16 on 1 inverter74.88 kWp1.25
2 inverters, fully loaded25616 strings of 16 on 2 inverters149.76 kWp1.25
4 inverters, fully loaded51232 strings of 16 on 4 inverters299.52 kWp1.25