Tesla TSP-420 with SMA SB5.0-1SP-US-41

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 4–13 panels work. The longest string reaches 581 V on the coldest morning, under the 600 V inverter limit. One SMA SB5.0-1SP-US-41 takes up to 1 string of 13: 13 panels, 5.46 kWp DC, DC/AC ratio 1.09.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C4–12 panels per string (best 12)
Chicago, IL−21 °C4–13 panels per string (best 13)
Denver, CO−23.6 °C4–13 panels per string (best 13)
Atlanta, GA−9.5 °C4–13 panels per string (best 13)
Dallas, TX−7.1 °C4–13 panels per string (best 13)
Phoenix, AZ1.3 °C4–13 panels per string (best 13)
Miami, FL5.9 °C4–13 panels per string (best 13)

Common system sizes

How Tesla TSP-420 panels lay out on the SMA SB5.0-1SP-US-41 for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW142 strings of 7 on 1 inverter5.88 kWp1.18
About 8 kW191 × 10 + 1 × 9 panels on 2 inverters7.98 kWp0.80
About 10 kW242 strings of 12 on 2 inverters10.08 kWp1.01