Home › Compatibility › Trina Solar TSM-435NE09RH05 + EG4 18kPV-12LV

Trina Solar TSM-435NE09RH05 with EG4 18kPV-12LV

Compatibility and string sizing for this panel and hybrid inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 6–16 panels work. The longest string reaches 598 V on the coldest morning, under the 600 V inverter limit. One EG4 18kPV-12LV takes up to 3 strings of 15: 45 panels, 19.57 kWp DC, DC/AC ratio 1.63.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C6–15 panels per string (best 14)
Chicago, IL−21 °C6–15 panels per string (best 14)
Denver, CO−23.6 °C6–15 panels per string (best 14)
Atlanta, GA−9.5 °C6–16 panels per string (best 15)
Dallas, TX−7.1 °C6–16 panels per string (best 15)
Phoenix, AZ1.3 °C6–16 panels per string (best 15)
Miami, FL5.9 °C6–16 panels per string (best 16)

Common system sizes

How Trina Solar TSM-435NE09RH05 panels lay out on the EG4 18kPV-12LV for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW141 string of 14 on 1 inverter6.09 kWp0.51
About 8 kW182 strings of 9 on 1 inverter7.83 kWp0.65
About 10 kW231 × 12 + 1 × 11 panels on 1 inverter10.01 kWp0.83