Trina Solar TSM-435NE09RH05 with EG4 FlexBOSS21
Compatibility and string sizing for this panel and hybrid inverter, calculated from both datasheets.
Compatible
Yes. At a −10 °C record low and a 40 °C hot day, strings of 7–16 panels work. The longest string reaches 598 V on the coldest morning, under the 600 V inverter limit. One EG4 FlexBOSS21 takes up to 3 strings of 13: 39 panels, 16.96 kWp DC, DC/AC ratio 1.06.
How it's calculated
NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.
- Voc on the coldest morning34.5 V × (1 + -0.239%/°C × (−10 − 25)) = 37.39 V per panel.
- Vmp on the hottest afternoonCells reach 71.8 °C (40 °C air plus the NMOT rise), so Vmp drops from 29.1 V to 24.37 V (Vmp coefficient taken as Pmax − Isc coefficient).
- Longest string600 V inverter limit ÷ 37.39 V = 16 panels.
- Shortest string120 V MPPT minimum ÷ 24.37 V = 5 panels; start-up voltage needs 7.
- Strings per MPPTHot-day Isc 16.24 A per string, so the MPPT inputs take 1 + 1 + 1 string(s).
By climate
The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.
| City | Record low | Result |
|---|---|---|
| Minneapolis, MN | −27 °C | 7–15 panels per string (best 12) |
| Chicago, IL | −21 °C | 7–15 panels per string (best 13) |
| Denver, CO | −23.6 °C | 7–15 panels per string (best 12) |
| Atlanta, GA | −9.5 °C | 7–16 panels per string (best 13) |
| Dallas, TX | −7.1 °C | 7–16 panels per string (best 13) |
| Phoenix, AZ | 1.3 °C | 7–16 panels per string (best 13) |
| Miami, FL | 5.9 °C | 7–16 panels per string (best 14) |
Common system sizes
How Trina Solar TSM-435NE09RH05 panels lay out on the EG4 FlexBOSS21 for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.
| System | Panels | Layout | DC size | DC/AC |
|---|---|---|---|---|
| 1 inverter, fully loaded | 48 | 3 strings of 16 on 1 inverter | 20.88 kWp | 1.30 |
| 2 inverters, fully loaded | 96 | 6 strings of 16 on 2 inverters | 41.76 kWp | 1.30 |
| 4 inverters, fully loaded | 192 | 12 strings of 16 on 4 inverters | 83.52 kWp | 1.30 |