Home › Compatibility › Trina Solar Vertex S+ TSM-440NEG9R.28 + Solis S6-GC60K-US

Trina Solar Vertex S+ TSM-440NEG9R.28 with Solis S6-GC60K-US

Compatibility and string sizing for this panel and string inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 5–17 panels work. The longest string reaches 962 V on the coldest morning, under the 1000 V inverter limit. One Solis S6-GC60K-US takes up to 8 strings of 17: 136 panels, 59.84 kWp DC, DC/AC ratio 1.00.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C5–17 panels per string (best 17)
Chicago, IL−21 °C5–17 panels per string (best 17)
Denver, CO−23.6 °C5–17 panels per string (best 17)
Atlanta, GA−9.5 °C5–17 panels per string (best 17)
Dallas, TX−7.1 °C5–17 panels per string (best 17)
Phoenix, AZ1.3 °C5–18 panels per string (best 18)
Miami, FL5.9 °C5–18 panels per string (best 18)

Common system sizes

How Trina Solar Vertex S+ TSM-440NEG9R.28 panels lay out on the Solis S6-GC60K-US for one, two and four fully loaded inverters, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
1 inverter, fully loaded1368 strings of 17 on 1 inverter59.84 kWp1.00
2 inverters, fully loaded27216 strings of 17 on 2 inverters119.68 kWp1.00
4 inverters, fully loaded54432 strings of 17 on 4 inverters239.36 kWp1.00