Home › Calculators › Conduit fill

Conduit fill calculator

List the conductors going into one raceway and get the smallest trade size that stays within NEC Chapter 9 fill limits. PV wire has no NEC table area, so enter its outside diameter from the spec sheet.

How it works

Each conductor's area comes from NEC Chapter 9 Table 5 (insulated) or Table 8 (bare). The total is compared with the raceway's internal area from Table 4, using the fill limits in Chapter 9 Table 1: 53% for one conductor, 31% for two and 40% for three or more. A nipple of 24 in or less may be filled to 60%.

Equipment grounding conductors count toward fill. PV wire and USE-2 are not in Table 5, so their area comes from the manufacturer's outside diameter: area = π × diameter² ÷ 4.

Fill is only one check. More than three current-carrying conductors in the same raceway also lower their ampacity, which the wire size calculator takes into account.

Questions

How many 10 AWG THHN fit in 3/4 in EMT?

Ten. 40% of 3/4 in EMT is 0.213 in², and each 10 AWG THHN is 0.0211 in², so ten fit (0.211 in²). Use the calculator for your exact mix.

Do I count the ground wire in conduit fill?

Yes. Equipment grounding conductors count toward fill, but not toward the number of current-carrying conductors used for ampacity adjustment.

Estimates only, based on NEC 2020/2023 tables. Check the code edition your jurisdiction uses, the equipment datasheets and your AHJ before you build.