How it works
Each conductor's area comes from NEC Chapter 9 Table 5 (insulated) or Table 8 (bare). The total is compared with the raceway's internal area from Table 4, using the fill limits in Chapter 9 Table 1: 53% for one conductor, 31% for two and 40% for three or more. A nipple of 24 in or less may be filled to 60%.
Equipment grounding conductors count toward fill. PV wire and USE-2 are not in Table 5, so their area comes from the manufacturer's outside diameter: area = π × diameter² ÷ 4.
Fill is only one check. More than three current-carrying conductors in the same raceway also lower their ampacity, which the wire size calculator takes into account.