Home › Dubai
Solar design tools for Dubai (DEWA)
The Tera Labs tools, set up for DEWA's Shams Dubai / DRRG rules instead of the US electrical code: array voltage at 0 °C, 600 V villa and 1,000 V building limits, 50 °C ambient, string fuses, DEWA's cable table and the connected-load capacity limit.
DEWA rules these tools apply
- Voltage at 0 °C. DRRG Standards 2.1: the maximum array voltage is worked out at a minimum outdoor temperature of 0 °C. Max 1,000 V DC on buildings and 600 V DC on private villas; 1,500 V only for canopies and urban structures that are not on a building.
- 50 °C ambient. Equipment is rated for a 50 °C maximum outdoor temperature. Cell temperature on the hottest day comes from the PVsyst thermal model with the loss factor for your roof type.
- String fuses. DRRG Standards 2.6.1: needed when (strings in parallel − 1) × Isc is above the panel's max series fuse rating, sized between 1.5 and 2.4 × Isc.
- Capacity. Connection Conditions 2.2: the system's AC capacity is limited by the building's total connected load in slabs (100% of the first 100 kW, 75% of the next 100 kW, 50% up to 400 kW, 25% up to 600 kW, 5% above), up to 1,000 kW per plot.
- Eligible equipment. Panels and inverters must be on DEWA's eligible equipment list. The tools mark the models that were on it when we last checked (26 Nov 2026).
Abu Dhabi, Sharjah, the Northern Emirates, Saudi Arabia, Oman, Bahrain and Qatar: all Gulf solar tools.