Solar design tools for the Gulf
String sizing and project planning for the UAE, Saudi Arabia, Oman, Bahrain and Qatar, each set up for its own utility rules: design temperatures, DC voltage limit, string fuses, capacity and equipment approval. Free, in the browser, with the same datasheet library as the US tools.
Dubai (DEWA)
DRRG voltage classes, string fuses, DEWA cable table, TCL capacity slabs and the eligible equipment list.
Open →Abu Dhabi (DoE / ADDC / AADC)
0 °C / 50 °C (UAE practice) · No fixed cap; self-supply, exports not netted.
Open →Sharjah (SEWA)
0 °C / 50 °C (UAE practice) · Written SEWA approval before energising.
Open →Northern Emirates (Etihad WE)
0 °C or lower / 50 °C · 1 MW per premises; 10 kW per phase single-phase.
Open →Saudi Arabia (SEC / SERA)
−5 °C / 55 °C (SEC Annex D) · 1 kW to 2 MW per premises; ≤ 11 kW single-phase.
Open →Oman (Sahim)
0 °C / 50 °C (UAE practice) · No published cap; exports paid at the Bulk Supply Tariff.
Open →Bahrain (EWA)
0 °C / 50 °C (conservative) · Net metering for homes ≤ 100 kW; net billing above.
Open →Qatar (Kahramaa)
0 °C / 50 °C (conservative) · ≤ contracted demand, max 25 MW; 0.237 QAR/kWh export.
Open →Rules side by side
| Market | Scheme / rules | Design temps (min / max) | DC voltage limit | Capacity | Equipment |
|---|---|---|---|---|---|
| Dubai | DEWA Shams Dubai (DRRG) | 0 °C / 50 °C | 1,000 V buildings, 600 V villas, 1,500 V canopies | TCL slabs, max 1 MW per plot | DEWA eligible list (marked in the tools) |
| Abu Dhabi | DoE Self-Supply Policy (2026) | 0 °C / 50 °C (UAE practice) | Not stated: equipment class | No fixed cap; self-supply, exports not netted | Distribution Code; confirm with ADDC / AADC |
| Sharjah | SEWA approval (no general scheme yet) | 0 °C / 50 °C (UAE practice) | Not stated: equipment class | Written SEWA approval before energising | IEC + ECAS; confirm with SEWA |
| Northern Emirates | Etihad WE DSS Standards (2024) | 0 °C or lower / 50 °C | 1,500 V at 0 °C on buildings | 1 MW per premises; 10 kW per phase single-phase | Etihad WE approved list |
| Saudi Arabia | SEC small-scale PV standards; SERA framework | −5 °C / 55 °C (SEC Annex D) | Not stated: equipment class (1.5 kV cables) | 1 kW to 2 MW per premises; ≤ 11 kW single-phase | SASO conformity + Annex E standards |
| Oman | Sahim (APSR / Nama) | 0 °C / 50 °C (UAE practice) | Not stated: equipment class | No published cap; exports paid at the Bulk Supply Tariff | Confirm with Nama |
| Bahrain | EWA net metering / net billing | 0 °C / 50 °C (conservative) | Not stated: equipment class | Net metering for homes ≤ 100 kW; net billing above | EWA renewable equipment list (marked in the tools) |
| Qatar | Kahramaa BeSolar | 0 °C / 50 °C (conservative) | Not stated: equipment class (1.5 kV cables) | ≤ contracted demand, max 25 MW; 0.237 QAR/kWh export | Kahramaa approved makers and series (marked in the tools) |
Checked 26 Nov 2026. Where an authority publishes no value, the tools use UAE practice (0 °C and 50 °C) or IEC 62548 and say so on the page. Kuwait has no retail rooftop scheme yet.