Solar design tools for Sharjah (SEWA)
The Tera Labs tools, set up for Sharjah (SEWA): array voltage at 0 °C, 50 °C ambient, the 1,000 V or 1,500 V class, IEC 62548 string fuses and SEWA's capacity rule.
Sharjah rules these tools apply
- Design temperatures. SEWA publishes no design temperature. The tool uses 0 °C for the maximum string voltage and 50 °C ambient, the values DEWA and Etihad WE set for the UAE.
- Voltage limit. SEWA has not published a rooftop DC voltage limit. Pick the 1,000 V or 1,500 V class that matches your panels and inverter; the tool also checks the inverter's maximum DC input and the panel's maximum system voltage.
- String fuses. Outside Dubai the tools use the IEC 62548 check, written the same way as DEWA's DRRG 2.6.1: string fuses are needed when (strings in parallel − 1) × the panel's short-circuit current is above its maximum series fuse rating. gPV fuses are then rated between 1.5 and 2.4 × Isc and no higher than the panel's fuse rating. Some editions add a safety factor to Isc, so near the limit check the edition your authority uses.
- Capacity and scheme. SEWA had not opened a general rooftop net-metering scheme when we checked (November 2026). Any grid-tied system needs SEWA's written approval and a connection agreement before it is energised.
- Equipment. Use IEC-certified equipment (IEC 61215 and 61730 panels, IEC 62109 and 62116 inverters) with ECAS conformity, and confirm acceptance with SEWA.