Solar design tools for Bahrain (EWA)
The Tera Labs tools, set up for Bahrain (EWA): array voltage at 0 °C, 50 °C ambient, the 1,000 V or 1,500 V class, IEC 62548 string fuses and EWA's capacity rule.
Bahrain rules these tools apply
- Design temperatures. EWA publishes no design temperature online. 0 °C is a conservative minimum for Bahrain, and equipment is checked at 50 °C ambient.
- Voltage limit. EWA's online guidance doesn't state a DC voltage limit. Pick the 1,000 V or 1,500 V class that matches your panels and inverter; the tool also checks the inverter's maximum DC input and the panel's maximum system voltage.
- String fuses. Outside Dubai the tools use the IEC 62548 check, written the same way as DEWA's DRRG 2.6.1: string fuses are needed when (strings in parallel − 1) × the panel's short-circuit current is above its maximum series fuse rating. gPV fuses are then rated between 1.5 and 2.4 × Isc and no higher than the panel's fuse rating. Some editions add a safety factor to Isc, so near the limit check the edition your authority uses.
- Capacity and scheme. Homes up to 100 kW are on net metering: surplus is carried forward to later months. Systems above 100 kW, and all non-residential systems, are on net billing: surplus is sold to EWA. Applications go through the Benayat portal.
- Equipment. Panels and inverters must be on EWA's renewable equipment list, installed by an EWA-approved contractor and designed by an approved engineering office. The tools mark models on the list as EWA list (checked 26 Nov 2026).
Other markets: all Gulf solar tools.