REC REC420AA Pure-R with EG4 18kPV-12LV

Compatibility and string sizing for this panel and hybrid inverter, calculated from both datasheets.

✓

Compatible

Yes. At a −10 °C record low and a 40 °C hot day, strings of 4–9 panels work. The longest string reaches 579 V on the coldest morning, under the 600 V inverter limit. One EG4 18kPV-12LV takes up to 4 strings of 9: 36 panels, 15.12 kWp DC, DC/AC ratio 1.26.

How it's calculated

NEC 690.7 coefficient method with the datasheet values. Record low −10 °C, hottest day 40 °C.

By climate

The coldest morning sets the longest string. Record lows are ASHRAE extreme annual mean minimums; the hottest day is kept at 40 °C.

CityRecord lowResult
Minneapolis, MN−27 °C4–9 panels per string (best 8)
Chicago, IL−21 °C4–9 panels per string (best 8)
Denver, CO−23.6 °C4–9 panels per string (best 8)
Atlanta, GA−9.5 °C4–9 panels per string (best 9)
Dallas, TX−7.1 °C4–9 panels per string (best 9)
Phoenix, AZ1.3 °C4–9 panels per string (best 9)
Miami, FL5.9 °C4–9 panels per string (best 9)

Common system sizes

How REC REC420AA Pure-R panels lay out on the EG4 18kPV-12LV for typical 6, 8 and 10 kW home systems, using the String Sizer's project calculator at the same −10 °C / 40 °C design temperatures.

SystemPanelsLayoutDC sizeDC/AC
About 6 kW142 strings of 7 on 1 inverter5.88 kWp0.49
About 8 kW191 × 7 + 2 × 6 panels on 1 inverter7.98 kWp0.67
About 10 kW243 strings of 8 on 1 inverter10.08 kWp0.84