Section 690.7 of the National Electrical Code (NEC) sets the maximum voltage of a PV system's DC circuits. It is the number your inverter input, your conductors, your disconnects and the modules themselves all have to be rated for. Because panel voltage rises as temperature drops, the maximum voltage is not the voltage printed on the datasheet. It is the voltage on the coldest morning the site is expected to see.
The limits: 600 V, 1000 V and 1500 V
The 2023 NEC caps the DC voltage by where the array is:
- One- and two-family dwellings: 600 V. This is why most residential string inverters (SMA Sunny Boy, Fronius Primo, SolarEdge, Sol-Ark) have a 500 V or 600 V maximum input.
- Other buildings (commercial, industrial, multifamily): 1000 V.
- Ground-mounted systems that are not on or in buildings: up to 1500 V, under the wiring rules of 690.31.
The array also has to stay under every component's own rating: the inverter's maximum DC input voltage and the module's maximum system voltage (usually 1000 V or 1500 V on the panel datasheet). The lowest of these is the limit you design to.
Method 1: the manufacturer's temperature coefficient
690.7(A) lets you correct the open-circuit voltage (Voc) using the module's own temperature coefficient. This is the most accurate method and the one most designers use:
β_Voc is the Voc temperature coefficient from the datasheet (a negative number, in %/°C) and T_min is the lowest expected ambient temperature. The usual source for T_min is the ASHRAE extreme annual mean minimum design temperature for the nearest weather station, which is the value Tera Labs looks up when you pick a city.
Example: a Qcells Q.TRON BLK M-G2+ 430 has Voc = 39.32 V and β_Voc = −0.24 %/°C. Denver's design low is −23.6 °C:
Method 2: Table 690.7(A)
For crystalline and multicrystalline silicon modules, the code also gives a table of correction factors by ambient temperature. You multiply the nameplate Voc by the factor for your lowest expected temperature. The factors run from 1.02 at 24 to 20 °C up to 1.25 at −36 to −40 °C; for example, −16 to −20 °C is 1.18 and −21 to −25 °C is 1.20.
The table is deliberately conservative because it has to cover every silicon module. Modern TOPCon and heterojunction panels have much smaller voltage coefficients than the table assumes, so the table overstates their cold voltage.
Method 3: engineered design (100 kW and up)
For systems of 100 kW or more, a licensed professional electrical engineer may document the maximum voltage with an industry-standard calculation method and stamp it. This mostly matters for large commercial and utility projects.
Why the method changes your string length
On a Sol-Ark 15K (500 V maximum DC input) in Denver:
- Coefficient method: 500 ÷ 43.91 = 11.4, so 11 panels per string (483 V).
- Table method: 500 ÷ 47.18 = 10.6, so 10 panels per string.
Both are code-compliant. The coefficient method simply uses the information the manufacturer published for this exact module, which is why it usually allows one more panel per string, and fewer strings and inputs for the same array.
What inspectors usually want to see
- The module datasheet with Voc and β_Voc highlighted.
- The temperature you used and its source (ASHRAE station and value).
- The corrected Voc per module, the number of modules in series, and the resulting string voltage compared with the inverter and module limits.
The String Sizer's printable report lists exactly these numbers for any panel, inverter and city.
Common mistakes
- Using the average January low instead of the design record low.
- Checking only the inverter limit and forgetting the 600 V residential cap or the module's own maximum system voltage.
- Applying the table to thin-film or other non-silicon modules it was not written for.
- Rounding the string count up instead of down.
Related guides
This guide is for education. Confirm every design with the manufacturer's instructions and sizing tools, current datasheets and your authority having jurisdiction (AHJ).