Planning a rooftop project in Saudi Arabia (SEC / SERA)
The physics is the same everywhere: Voc rises in the cold, Vmp falls in the heat, and each MPPT has current limits. What changes from market to market are the design temperatures, the voltage limit, the capacity rule and the equipment approval. This page applies SEC / SERA's rules where they are published, and IEC 62548 where they are not.
Design temperatures
Annex D of the SEC standards gives an outdoor ambient range of −5 °C to 55 °C, so the tool works out the string voltage at −5 °C and the hot-day voltage at 55 °C. Northern sites (Tabuk, Al-Jouf, Northern Borders) can get colder than −5 °C: use your site's record low there.
Voltage limit
SEC's Standards for the Connection of Small-Scale Solar PV Systems set no separate DC voltage limit; PV cables are specified for 1.5 kV DC (Annex E). Pick the 1,000 V or 1,500 V class that matches your panels and inverter; the tool also checks the inverter's maximum DC input and the panel's maximum system voltage.
For example, the Jinko Tiger Neo 3.0 JKM650N-66QL6-BDV has a Voc of 50.26 V and a coefficient of −0.24 %/°C. At −5 °C: 50.26 × [1 + 0.0024 × 30] = 53.88 V per panel, so up to 18 under a 1,000 V class and 27 under 1,500 V, if the inverter and panel are rated for it (20 on a common 1,100 V inverter). Pick your panel and inverter above for the exact answer.
Hot side and MPPT window
On the hottest day the cells run well above the air. The tool uses the PVsyst thermal model, Tcell = Tamb + 0.9 × 1000 × (1 − η) ÷ Uc, with Uc 20 for sheet roofs, 25 for concrete (RCC) roofs and 29 for carports, then checks that Vmp at that temperature stays above the inverter's MPPT minimum.
String fuses
Outside Dubai the tools use the IEC 62548 check, written the same way as DEWA's DRRG 2.6.1: string fuses are needed when (strings in parallel − 1) × the panel's short-circuit current is above its maximum series fuse rating. gPV fuses are then rated between 1.5 and 2.4 × Isc and no higher than the panel's fuse rating. Some editions add a safety factor to Isc, so near the limit check the edition your authority uses.
Capacity and scheme
Small-scale systems run from 1 kW to 2 MW per premises (section 4), within the Maximum Connected Capacity set under SERA's regulations (section 6.1). Single- and two-phase inverters are allowed only up to 11 kW (section 6.9.7.5).
Equipment approval
SEC keeps no equipment list. Panels and inverters need SASO conformity, and inverters must meet the standards in Annex E: IEC 62109-1/-2, IEC 62116, IEC TS 62910 and IEC 62920.
Sources
Rules checked 26 Nov 2026. These are planning tools, not a utility submission: always check the rules and lists in force before you apply.