Most home solar systems connect to the house through a breaker in the main electrical panel, called a backfeed breaker. The panel's busbar is then fed from two directions: the utility through the main breaker, and the solar inverter through its breaker. The 120% rule limits how much the solar side can add so the busbar is never overloaded.
The rule
Under NEC 705.12(B)(3)(2), when the solar breaker is at the opposite end of the busbar from the main breaker:
The 125% factor treats the inverter's output as a continuous load. The extra 20% allowance on the busbar is safe because, with the sources at opposite ends, current from the two sources cannot all flow through the same section of busbar.
The classic 200 A example
A 200 A panel with a 200 A main breaker:
That is exactly why inverters such as the SMA Sunny Boy 7.7-US (7,680 W, 32 A) and the many "7.6 kW" models are so common: they are the largest that fit a standard 200 A panel with a 200 A main and a 40 A backfeed breaker.
When the system is bigger
A Sol-Ark 15K has a maximum continuous output of about 62.5 A at 240 V, so 125% is about 78 A, well over the 40 A available. A 225 A busbar with a 200 A main gives 270 − 200 = 70 A, still not enough. The options are:
- Downsize the main breaker: a 150 A main on a 200 A busbar leaves 240 − 150 = 90 A, enough for the 15K. Only possible if a load calculation shows the house can live with a 150 A main.
- Upgrade the panel: a new panel with a larger busbar.
- Supply-side connection: connect the inverter between the meter and the main breaker (NEC 705.11), which avoids the busbar rule entirely but needs its own disconnect and overcurrent protection and is often subject to utility rules.
- Sum-of-breakers method: NEC 705.12(B)(3)(3) allows a panel where the sum of all breakers, excluding the main, stays within the busbar rating. This suits a dedicated subpanel more than a main panel.
Things that trip people up
- The backfeed breaker must be at the opposite end of the busbar from the main to use the 120% allowance, and it must be labelled.
- Use the inverter's maximum continuous output current from the datasheet, not its power divided by a guessed voltage.
- Several inverters (for example several microinverter branch circuits) add together.
- Many utilities and AHJs have their own interconnection rules on top of the NEC.
The 120% rule calculator checks any panel, main breaker and inverter combination, and the panel load calculator helps decide whether downsizing the main breaker is realistic.
Related guides
This guide is for education. Confirm every design with the manufacturer's instructions and sizing tools, current datasheets and your authority having jurisdiction (AHJ).